10k V 继电保护装置的运行维护研究

Study on operati on and maintenance of 10kV relay p r otecti on equi pment

焦玉振

J I A O Yu 2zhen

(河南省社旗县电业局,河南社旗 473300)(Henan Sheqi Power Bureau,Sheqi 473300,China )

摘 要:10k V 继电保护装置的运行维护是电力系统的一个重要部分,它能否安全、稳定、可靠地运行,直接关系到整个系统的正常运行。对10k V 继电保护装置的运行维护进行了研究,给出了其运行维护实际操作时应注意的问题。

关键词:10k V 继电器;继电器保护装置;运行维护

中图分类号:T M 712   文献标志码:B    文章编号:1674-1951(2008)12-0073-02

Abstract:10k V relay p r otecti on equi pment is i m portant part of power syste m,and its safe,stable and reliable oper 2ati on is significant for hole syste m nor mal operati on .The operati on and maintenance of 10k V relay p r otecti on equi p 2ment were studied,and s ome p r oblem s needing attenti on in p ractical operati on were pointed out .Key words:10k V relay;p r otecti on equi pment of relay;operati on and maintenance

收稿日期:2008-09-28

  10kV 供电系统是电力系统的一部分,它能否安全、稳定、可靠地运行,直接关系到电力系统能否

正常的运行。电力系统是由发电、变电、输电、配电和用电等5个环节组成的。在电力系统中,各种类型的、大量的电气设备通过电气线路紧密地联结在一起。由于其覆盖的地域极其辽阔、运行环境极其复杂以及各种人为因素的影响,电气故障的发生是不可避免的。在电力系统中的任何一处发生事故,都有可能对电力系统的运行产生重大影响。其中最为常见、危害最大的应属各种类型的短路事故。一旦出现短路故障,电流将急剧增大、电压将急剧下降、电压与电流之间的角相位将急剧变化,所以,继电保护装置的运行维护显得尤为重要。本文对10k V 继电保护装置的运行维护进行了探讨并给出其运行维护实际操作时的注意问题。

1 10kV 继电保护装置

在电力系统中以物理量的变化为基础,利用正

常运行和故障时各物理量的差别就可以构成各种不同原理和类型的继电保护装置。反映电流变化的电流保护有定时限过电流保护、反时限过电流保护、电流速断保护、过负荷保护和零序电流保护等;反映电压变化的电压保护有过电压保护和低电压保护;既反映电流的变化又反映电压与电流之间相位角变化的方向过电流保护;反映电压与电流之间比值,也就是反映短路点到保护安装处阻抗的距离保护;反映输入电流与输出电流之差的差动保护,其中又分为横联差动和纵联差动保护;用于反映系统中频率变化的周波保护;专门用于反映变压器内部故障的气体保护(即瓦斯保护),其中又分为轻瓦斯和重瓦斯保护;专门用于反映变压器温度变化的温度保护等。另外,10k V 系统中一般可在进线处装设电流保护,在配电变压器的高压侧装设电流保护、温度保护(油浸变压器根据其容量大小还应考虑装设气体保护),高压母线分段处应根据具体情况装设电流保护等。

按照10kV 供电系统的设计规范

[1]

要求,在10

kV 供电线路、

配电变压器和分段母线上一般应设置

10kV继电保护装置的运行维护研究